CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
173 63-4528—04
05 Motor Parameters ~ The parameter can be set during operation
Induction Motor
Start auto tuning by pressing the Run key, and the measured value will be written into motor 1 automatically.
AUTO-Tuning Process (dynamic motor):
1. Make sure that all the parameters are set to factory settings and the motor wiring is correct.
2. Make sure the motor has no-load before executing auto-tuning and the shaft is not connected to any belt or gear
motor. It is recommended to set to 2 if the motor can’t separate from the load.
3. Set Pr.05-00=1 and press the Run key; the drive will begin auto-tuning. Please be aware motor starts spinning when
the Run key is pressed.
4. When auto-tuning is complete, please check if the measured values are written into motor 1 automatically.
NOTE: If Pr.05-00 is set to 2, it needs to input Pr.05-05 for motor 1.
NOTES:
1. In torque/vector control mode, it is not recommended to have motors run in parallel.
2. It is not recommended to use torque/vector control mode if motor rated power exceeds the rated power of the VFD
This value should be set according to the rated frequency of the motor as indicated on the motor nameplate. The factory
setting is 90% X rated current
Example: The rated current for 7.5HP (5.5kW) is 25 and factory setting is 22.5A. The range for setting will be
10~30A.(25*40%=10A and 25*120%=30A)
05 - 00 Motor Auto Tuning
Factory Setting: 0
Settings 0: No function
1: Measure induction motor in dynamic status (motor spinning)
2: Measure induction motor in static status (motor not spinning)
Motor 1
Motor Rated
Frequency
01-01
Motor Rated Voltage 01-02
Motor Full-load
Current
05-01
Motor Rated Power 05-02
Motor Rated Speed 05-03
Motor Pole Numbers 05-04
05 - 01 Full-Load Current of Induction Motor 1 (A)
Unit: Ampere
Factory Setting: 0
Settings 10 to 120% of drive’s rated current