CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
63-4528—04 174
• It is used to set rated power of the motor 1. The factory setting is the power of the drive
• It is used to set the rated speed of the motor and need to set according to the value indicated on the motor nameplate.
• It is used to set the number of motor poles (must be an even number).
• Factory setting is 40% of the drive’s rated current.
• It is used to set the rated speed of the motor and need to set according to the value indicated on the motor nameplate.
• Pr. 05-06 and Pr.05-07 are used to record the motor operation time. They can be cleared by setting to 00 and time won’t be
recorded when it is less than 60 seconds
a
05 - 02 Rated Power of Induction Motor 1(kW)
Factory Setting: 0
Settings 0~655.35 kW
a
05 - 03 Rated Speed of Induction Motor 1 (rpm)
Factory Setting:
1710: 60Hz 4 poles
1410: 50Hz 4 poles
Settings 0~65535
05 - 04 Pole Number of Induction Motor 1
Factory Setting: 4
Settings 2~20
05 - 05 No-load Current of Induction Motor 1 (A)
Unit: Ampere
Factory Setting: 0
Settings 0 to the factory setting in Pr.05-01
Settings 0~65535
05 - 06 Accumulative Motor Operation Time (Min)
Factory Setting: 0
Settings 0~1439
05 - 07 Accumulative Motor Operation Time (Day)
Factory Setting: 0
Settings 00~1440