CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
63-4528—04 178
• It is used to set the accel./decel. time selection when stall prevention occurs at constant speed
• When Pr.06-05 and Pr.06-08 are set to 1 or 3, it will display a warning message and won’t have an abnormal record.
• When Pr.06-05 and Pr.06-08 are set to 2 or 4, it will display a warning message and will have an abnormal record.
a
06 - 04 Accel./Decel. Time Selection of Stall Prevention at Constant Speed
Factory Setting: 0
Settings 0: by current accel/decel time
1: by the 1st accel/decel time
2: by the 2nd accel/decel time
3: by the 3rd accel/decel time
4: by the 4th accel/decel time
5: by auto accel/decel
a
06 - 05 Over-torque Detection Selection (OT1)
Factory Setting: 0
Settings 0: Disable
1: Over-torque detection during constant speed operation, continue to operate after detection
2: Over-torque detection during constant speed operation, stop operation after detection
3: Over-torque detection during operation, continue to operate after detection
4: Over-torque detection during operation, stop operation after detection
a
06 - 08 Over-torque Detection Selection (OT2)
Factory Setting: 0
Settings 0: Disable
1: Over-torque detection during constant speed operation, continue to operate after detection
2: Over-torque detection during constant speed operation, stop operation after detection
3: Over-torque detection during operation, continue to operation after detection
4: Over-torque detection during operation, stop operation after detection
a
06 - 06 Over-torque Detection Level (OT1)
Factory Setting: 120
Settings 10 to 250% (100%: drive’s rated current)
a
06 - 07 Over-torque Detection Level (OT1
Factory Setting: 0.1
Settings 0.0~60.0 seconds
a
06 - 09 Over-torque Detection Level (OT2)
Factory Setting: 120
Settings 10~200%, 100% drive’s rated current
a
06 - 10 Over-torque Detection Time (OT2)
Factory Setting: 0.1
Settings 0.0~60.0?