CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
191 63-4528—04
• Pr.06-53 to Pr.06-58 are used to record the operation time for 6 malfunctions and it can also check if there is any wrong with
the drive according to the internal time.
• When the malfunction occurs during operation, it records fault in Pr.06-16~06-21 and operation time is recorded in Pr.06-
53~06-58.
06 – 47 PT100 Detection Level 1
Factory Setting: 5.000
Settings 0.00~10.00V
06 - 48 PT100 Detection Level 2
Factory Setting: 7.000
Settings 0.00~10.00V
06 – 49 PT100 Level 1 Frequency Protection
Factory Setting: 0.00
Settings 0.00~600.00 Hz
06 - 50 Software Detection GFF Current Level
Factory Setting: 60.0
Settings 0.0~6553.5%
06 - 51 Software Detection GFF Filter Time
Factory Setting: 0.10
Settings 0.0~655.35
06 - 52 Disable Level of dab
Factory Setting: 180.0/360.0
Settings 230V models: 0.0~220.0 Vdc
460V models 0.0~440.0 Vdc
06 - 53 Fault Record 1 (min)
06 - 54 Fault Record 2 (min)
06 - 55 Fault Record 3 (min)
06 - 56 Fault Record 4 (min)
06 - 57 Fault Record 5 (min)
06 - 58 Fault Record 6 (min)
Factory Setting: Read Only
Settings 0~65535 minutes