CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
63-4528—04 192
For example: When the first fault ovA occurs after operation 3000 min., second fault ovd occurs at 3482 min., third fault ovA
occurs at 4051 min., fourth fault ocA at 5003 min., fifth fault ocA at 5824 min., sixth fault ocd occurs at 6402 min. and seven
fault ocS at 6951 min.
It will be recorded as the table below.
First Fault Pr.06-16 ovA Pr.06-53 3000
Second Fault Pr. 06-16 ovd Pr. 06-53 3482
Pr. 06-17 ovA Pr. 06-54 3000
Third Fault Pr. 06-16 ovA Pr. 06-53 4051
Pr. 06-17 ovd Pr. 06-54 3482
Pr. 06-18 ovA Pr. 06-55 3000
Seventh Fault Pr. 06-16 ocS Pr. 06-53 6951
Pr 06-17 ocA Pr 06-54 5824
Pr 06-18 ocA Pr 06-55 5003
Pr 06-19 ovA Pr 06-56 4051
Pr 06-20 ovd Pr 06-57 3482
Pr 06-21 ovA Pr 06-58 3000
06 - 59 Number of Days of Malfunction (V)
Factory Setting: Read Only
Settings Read Only
06 - 60 Duration of Malfunction
Factory Setting: Read Only
Settings Read Only
06 - 61 Low Current Setting Level
Factory Setting: 0.0
Settings 0.0 ~ 100.0%
06 - 62 Low Current Detecting Time
Factory Setting: 0.00
Settings 0.00 ~ 360.00 seconds