CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
193 63-4528—04
• This parameter needs to work with multi-input function terminal #58 or #59 and multi-output function terminal #53 and #54.
Setting is 0: Fire mode is disabled
Setting is 1: When there is a fire, motors will operate clockwise (U,V.W).
Setting is 2: When there is a fire, motors will operate counter-clockwise.
• This parameter is to set up the drive’s frequency when the fire mode is enabled.
• The settings of Pr06-66 to Pr06-69 decide if switch motors to operating under mains electricity.
06 - 63 Treatment for low current
Factory Setting: 0
Settings 0: No function
1: warn and coast to stop
2: warn and ramp to stop by 2
nd
deceleration time
3: warn and operation continue
06 - 64 Fire Mode
Factory Setting: 1
Settings 0: No Function
1: Forward Operation
2: Reverse Operation
06 - 65 Operating Frequency when running Fire Mode (hz)
Factory Setting: 6000
Settings 0.00 ~ 600.00 hz
06 - 66 Enable Bypass on Fire Mode
Factory Setting: 0.00
Settings 0: Disable Bypass
1: Enable Bypass
06 - 67 Bypass Delay Time on Fire Mode
Factory Setting: 0.00
Settings 0.00 ~ 6550.0 seconds
06 - 68 Auto-restart counter of Fire Mode
Factory Setting: 0.00
Settings 0 ~ 10
06 - 69 Length of Time to reset auto counter
Settings 0.00 ~ 6000.0sec Factory Setting: 0.00