EasyManua.ls Logo

Honeywell VFD CORE

Honeywell VFD CORE
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
63-4528—04 202
NOTE: For example, in textile machinery, you will hope that all the machines can be decelerated to stop to prevent bro-
ken stitching when power loss. In this case, the host controller will send a message to the VFD to use dEb func-
tion with deceleration time via EF.
Pr.07-14 to Pr.07-17 is for heavy load to prevent OV or OC occurs.
This parameter is used for the fan control.
Setting 0: Fan will be ON as the drive’s power is turned ON.
Setting 1: 1 minute after VFD stops, fan will be OFF
Setting 2: VFD runs and fan will be ON. VFD stops and fan will be OFF.
Setting 3: Fan run according to IGBT and capacitance temperature. Fan will be ON when preliminary capacitance temperature
is higher than 60
o
C. Fan will be OFF, when capacitance temperature is lower than 40
o
C.
Setting 4: Fan is always OFF
a
07 - 14 Dwell Time at Accel.
Factory Setting: 0.00
Settings 0.00~600.00 seconds
a
07 - 15 Dwell Frequency at Accel
Factory Setting: 0.00
Settings 0.00~600.00 seconds
a
07 - 16 Dwell Frequency at Accel.
Factory Setting: 0.00
Settings 0.00~600.00Hz
a
07 - 17 Dwell Frequency at Decel.
Factory Setting: 0.00
Settings 0.00~600.00 Hz
a
07 - 18 Fan Cooling Control
Factory Setting: 0
Settings 0: Fan always ON
1: 1 minute after the VFD stops, fan will be OFF
2: When the VFD runs, the fan is ON. When the VFD stops, the fan is OFF
3: Fan turns ON when preliminary heat sink temperature (around 60
o
C) is attained.
4: Fan always OFF
M33687
FREQUENCY
TIME
DWELL AT ACCEL./DECEL.
07-15
DWELL FREQ.
AT ACCEL.
07-14
DWELL
TIME AT
ACCEL.
07-16
DWELL
TIME AT
DECEL.
07-17
DWELL FREQ.
AT DECEL.

Related product manuals