CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
63-4528—04 212
09 Communication Parameters ~ The parameter can be set during the operation.
If the VFD is controlled by RS-485 serial communication, the communication address for this drive must be set via this
parameter. And the communication address for each VFD must be different and unique
This parameter is used to set the transmission speed between the RS485 master (PLC, PC, etc.) and VFD.
This parameter is set to how to react if transmission errors occur
It is used to set the transmission time between communication and keypad.
a
09 - 00 COM1 Communication Address
Factory Setting: 1
Settings 1~254
a
09 - 01 COM1 Transmission Speed
Factory Setting: 9.6
Settings 4.8~115.2kbits/s
a
09 - 02 COM1 Transmission Fault Treatment
Factory Setting: 3
Settings 0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and continue operation
a
09 - 03 COM1 Time-out Detection
Factory Setting: 0.0
Settings 0.0~100.0 seconds
0.0: Disable
a
09 - 04 COM1 Communication Protocol
Factory Setting: 1
Settings 1: 7, N, 2 for ASCII
2: 7,E, 1 for ASCII
3: 7, O, 1 for ASCII
M33697
SERIAL
COMMUNICATION
1:
+
EV
2: GND
3: SG –
4: SG
+
5: NC
6: NC
61
RS-485
WHEN COMTROLLING
BY COMMUNICATION,
CONNECT THE DRIVE
AND PC BY IFD6530 OR
IFD6500 CONVERTER