EasyManua.ls Logo

Honeywell VFD CORE

Honeywell VFD CORE
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 6: CONTROL CIRCUIT TERMINAL
63-4528—04 32
NOTE: Wire size of analog control signals: 18 AWG (0.75 mm
2
) with shielded wire
Analog input terminals (AVI 1, ACI, AVI 2, ACM)
Analog input signals are easily affected by external noise. Use shielded wiring and keep it as short as possible [less than 20
meters (65.6168 feet)] with proper grounding. If the noise is inductive, connecting the shield to terminal ACM can bring
improvement.
This way of using contacts in a circuit should be able to process weak signals at the bifurcated contacts. Do not use contacts
to control the terminal ACM.
If the analog input signals are affected by noise from the VFD, connect a capacitor and ferrite core as indicated in the following
diagram.
NOTE: The value of the capacitor is 0.1~0.01uF; if there is no noise issue, the capacitor is not necessary.
Digital inputs (FWD, REV, MI1~MI8, COM)
When using contacts or switches to control the digital inputs, use high quality components to avoid contact bounce.
Remove the Terminal Block
1. Loosen the screws using a screwdriver (see figure below).
S1
Factory setting: short-circuit
Power removal safety function for emergency stop.
SCM
SG+ Modbus RS-485
PIN 1,2,7,8: Reserved PIN 3, 6: GND
PIN 4: SG- PIN 5: SG+
SG-
Table 1. Control terminal specifications.
M33266
C
ACM
AVI1/ACI/AVI2
FERRITE CORE
M33267

Related product manuals