CHAPTER 10: DIGITAL KEYPAD
93 63-4528—04
Startup Wizard Guide
Follow the steps in the table below to complete the Startup Wizard.
Table 3. Honeywell Commissioning Start-Up Wizard
Screen
#
Screen
Verbiage
Screen Description Screen options
1 Boot Screen Honeywell displayed for 3 seconds N/A
2 Selection
Screen
Choose how to interact with the VFD:
Recommendation: Press function key F4 to start
the wizard
F4: Initials the START UP WIZARD
Menu: redirects to MAIN MENU
ESC: redirects to MONITOR Screen
3Select
Language
Choose the keypad programming language
Use UP and DOWN arrows to change from
default. Press ENTER to accept change.
F1 BACK up one menu (SAME function
throughout WIZARD)
F4 Next Parameter (SAME function throughout
WIZARD)
1. English (Default)
2. Spanish
3. Chinese
4. Portuguese
5. French
Use arrow keys to adjust. Press ENTER to save changes,
F4 to advance without changes.
4 Clock Time
and DATE
Select the time (Military) HH:MM:SS and date
YY/MM/DD
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
5 Motor
Voltage
Motor's rated voltage based upon Motor Name
Plate data
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
The default motor voltage is based on the VFD voltage that
you have selected
6 Motor
Current
Full Load AMPs (FLA)Do not use the motor
service factor amperage for this value.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
7 Motor FREQ Motor's rated frequency based upon Motor Name
Plate data
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
8 Motor RPM Motor's rated RPM based upon Motor Name
Plate data
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
9ACCEL
TIME
The time required to accelerate from the motor’s
current speed reference to a new speed
reference
Acceleration time is factory set for typical Fan and Pump
needs. Use arrow keys to adjust. Press ENTER to save
changes, F4 to advance without changes.
10 DECEL
TIME
The time required to decelerate from the motor’s
current speed reference to a new speed
reference
Decceleration time is factory set for typical Fan and Pump
needs. Use arrow keys to adjust. Press ENTER to save
changes, F4 to advance without changes.
11, 12,
13
PRESET
SPEED
1,2,3
Present Speed options. On digital input closure
the VFD will ignore the speed reference from the
analog input and will run at the programmed
speed.
With the use of MFI (Multifunction inputs) 1, 2, or 3 the drive
can be sent to the programmed speed on digital input
closure (Usage not required in the field). Adjust as needed
or press F4 to accept factory defaults.
14 Analog Input Select the speed reference signal type. 0. 0-10V - Use AVI (Analog Voltage Input terminal)
1. 4-20mA - Use ACI (Analog current input terminals)
2. 2-10V - Use AVI
3. 0-20mA - Use ACI
15 MIN
Frequency
The minimum frequency at which the motor will
operate
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
16 MAX
Frequency
The maximum frequency at which the motor will
operate
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
17 PRESS F4
to SAVE
ALL
Saves all parameter updates - VFD is ready to
operate
F1 will escape the user back to the Selection Screen again
F4 will save parameters and take the user to the display
screen