CHAPTER 11: SUMMARIES OF PARAMETER SETTINGS
63-4528—04 98
00-02 Parameter Reset
0: No function
1: Read only
6: Reset PLC (including CANopen Master Index)
7: Reset CANopen Index (Slave)
9: All parameters are reset to factory settings(base
frequency is 50Hz)
10: All parameters are reset to factory settings (base
frequency is 60Hz)
0
a
00-03 Start-up Display Selection
0: F (frequency command)
1: H (output frequency)
2: U (multi-function display, see Pr.00-04)
3: A (output current)
0
a
00-04
Content of Multi-function
Display (User Defined)
0: Display output current (A)
1: Display counter value (c)
2: Display actual output frequency (H.)
3: Display DC-BUS voltage (v)
4: Display output voltage (E)
5: Display output power angle (n)
6: Display output power in kW (P)
8: Display estimate output torque % (t)
10: Display PID feedback in % (b)
11: Display AVI1 in % (1.)
12: Display ACI in % (2.)
13: Display AVI2 in % (3.)
14: Display the temperature of IGBT in °C (i.)
15: Display the temperature of heat sink in °C (c.)
16: The status of digital input (ON/OFF) (i)
17: The status of digital output (ON/OFF) (o)
18: Multi-step speed (S)
19: The corresponding CPU pin status of digital input (d.)
20: The corresponding CPU pin status of digital output (0.)
25: Overload counting (0.00~100.00%) (h.)
26: Ground Fault GFF (Unit :%)( G.)
27: DC Bus voltage ripple (Unit: Vdc) (r.)
28: Display PLC data D1043 (C)
30: Display output of user defined (U)
31: H page x Pr.00-05 Display user Gain(K)
0
00-05
Coefficient Gain in Actual
Output Frequency
0~160.00 0
00-06 Software version
0.00~655.35
0
a
00-07
Parameter Protection
Password Input
0~65535
0~4 : Recording # of times of password attemps
0
a
00-08
Parameter Protection
Password Setting
0~65535
0 : No password protection / password is entered correctly
(Pr00-07)
1 : Parameter is locked
0
a
00-09 Display advanced parameters
Bit 0: Group 0
Bit 1: Group 1
Bit 2: Group 2
Bit 3: Group 3
Bit 4: Group 4
Bit 5: Group 5
Bit 6: Group 6
Bit 7: Group 7
Bit 8: Group 8
Bit 9: Group 9
0
00-10 Velocity Control Mode
0 : VF (V/F control)
2 : SVC (Sensor-Less Vector Control)
0
a
00-11 Loading mode selection
0 : Normal duty
1 : Heavy duty
0
Parameter Function Setting
Factory
Setting