Table 7 Example of Rack Load Calculations
BTU/hourTotal Volt-amps (VA)WeightHeight (U)QuantityComponent
Maximum
Heat
Dissipation
Typical
Heat
Dissipation
Maximum
Power
Consumption
Typical
Power
Consumption
(kg)(lbs)
426527631250810122270101c7000
enclosure
313931399209201125104BL460c Gen8
Server Blade
2422153571045017383.472D3700 SAS
disk enclosure,
containing 25
HDDs with
300GB, 6 GB
SAS protocol
per HDD
696696204204184122Rack-mounted
System
Console
686820203612Maintenance
switch
----81911CLIM patch
panel
----153338421Rack
(single-phase)
11998908835142664356792--Total
For a total thermal load for a system with multiple racks, add the heat outputs for all the racks in
the system.