58 HP ProLiant DL385 Server Maintenance and Service Guide
Hot-Plug Fan
WARNING: To reduce the risk of electric shock, personal
injury, and damage to the equipment:
Do not attempt to service any parts of the equipment other than
those specified in the following procedure. Any other activities
may require that you shut down the server and remove the
power cord.
•
•
•
Installation and maintenance of this product must be performed
by individuals who are knowledgeable about the procedures,
precautions and hazards associated with the product.
You must observe the following requirements when installing redundant hot-plug
fans:
To ensure optimum cooling, populate the primary fan locations, 2, 4, 5, 6,
and 7, before populating the redundant locations ("Identifying hot-plug fans"
on page 98
).
• If a primary fan fails, replace the non-functioning fan before installing fans
in redundant locations ("Identifying hot-plug fans" on page 98
).
To remove the component:
1. Extend or remove the server from the rack ("Extending the Server from the
Rack" on page 16
, "Removing the server from the rack" on page 18).
2. Remove the access panel ("Removing the access panel" on page 19
).
3. If the server is operating with less than seven functional fans, power down
the server ("Powering down the server" on page 17
), then continue with the
next step.