EasyManua.ls Logo

HT PQA400 - Page 136

HT PQA400
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PQA400 - PQA823 - PQA824
EN - 135
and that during the detectable time interval defined as:
32 x 5s = 160s.
32 x 78s = 2.5ms.
32 x 65s = 2.1ms.
the positive and negative difference (defined DELTA+ and DELTA- respectively) it’s over
the “windows” defined by the limit threshold set by user.
Based to the above description, downloading the saved data from meter to PC using the
standard TopView software, the below parameters are shown:
Num. Tot
Total number of recorded events.
Limit
Voltage value threshold defined by user which permits the recording
of a event.
Phase
ID of phase where the event is occurred.
Date/Time
Date/Hour in minutes, seconds, cents per second when the event is
occurred.
Up/Down
This flag is UP if the spike is correspondent to a rising edge and is
DOWN if the spike is correspondent to a falling edge.
PEAK+
Max positive value reached from spike during the detectable time
interval.
PEAK-
Mix negative value reached from spike during the detectable time
interval.
DELTA+
Max positive relative difference reached from spike during the
detectable time interval.
DELTA-
Min negative relative difference reached from spike during the
detectable time interval.
F/S
Type of event (F = FAST, S = SLOW).
For any detail about saved data please refer to TopView HELP ON LINE feature.
Shop for HT products online at:
1.877.766.5412
www.PowerMeterStore.com

Table of Contents

Related product manuals