7.2.1 Extinguishant Control Panel
The extinguishant control panel provides the following functions:
Two zones supported, a third zone congurable
Serial status connection and timer display
Hold activated indication and disablement indication
Test mode
Two
rst stage sounder outputs
One second-stage audible and visual alarm output
First- and second-stage relay contacts
Auxiliary 24 V DC output
Monitored manual release input and output
Monitored release pneumatic switch input
(Optional) Mode select key switch on the front panel
(Optional) Manual release on the front panel
The design and construction of the extinguishant control panel comply with EN 54
and EN 12094.
Figure 7-4 Extinguishant control panel
Table 7-1 Extinguishant control panel specications
Item
Specications
Input AC input frequency: ≤ 120 W
AC input voltage and frequency: 230 V AC (tolerance ±10%), 50 Hz
DC backup power voltage: 24 V DC
24 V power output 3 A
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 7 Fire Extinguishing System
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 93

Table of Contents

Other manuals for Huawei FusionDC1000A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionDC1000A and is the answer not in the manual?

Huawei FusionDC1000A Specifications

General IconGeneral
BrandHuawei
ModelFusionDC1000A
CategoryStorage
LanguageEnglish

Related product manuals