Figure 3-2 Appearance 2
(1) External horn strobe (2) Card reader
(3) End door (main entrance) (4) Air exhaust window
(5) Fire control box (6) Ground point
(7) Emergency door
3.2 Pre-fab. Module Thermal Insulation Structure
The pre-fab. module is furnished with a thermal insulation layer composed of steel
plates, bulk rock wool, and rock wool panels.
The pre-fab. module uses the rock wool sandwich panel structure for thermal
insulation. The protection structure uses the 100 mm thick
re-retardant level A1
rock wool material, which complies with the GB 8624-2012 design standard and
RoHS environmental protection directive, and meets the requirements for thermal
insulation and
re resistance.
3.3 Pre-fab. Module Coating
The current standard pre-fab. module coating solution passes the 1440-hour salt
spray test. According to the ISO12944 standard, the pre-fab. module provides the
VH protection level in C3 and C4 environments.
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 3 Structural system
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 14

Table of Contents

Other manuals for Huawei FusionDC1000A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionDC1000A and is the answer not in the manual?

Huawei FusionDC1000A Specifications

General IconGeneral
BrandHuawei
ModelFusionDC1000A
CategoryStorage
LanguageEnglish

Related product manuals