Loading...
2.3 Key Technical Specications
Table 2-3 Key technical specications
Conguration N+X-
Norma
l
Tempe
rature-
CE
N+X-
Low
Tempe
rature-
CE
2N-
Norma
l
Tempe
rature-
CE
2N-
Low
Tempe
rature-
CE
N+X-
Norma
l
Tempe
rature-
CCC
N+X
Low
Tempe
rature-
CCC
2N-
Norma
l
Tempe
rature-
CCC
2N-
Low
Temper
ature-
CCC
General
specic
ations
Applica
ble
temper
ature
range
–20°C
to
+55°C
–40°C
to
+45°C
–20°C
to
+55°C
–40°C
to
+45°C
–20°C
to
+55°C
–40°C
to
+45°C
–20°C
to
+55°C
–40°C
to
+45°C
Pre-fab.
module
dimensi
ons
12,192 mm x 2438 mm x 2896 mm
Power
supply
and
distribu
tion
architec
ture
N+X 2N N+X 2N
Total
power
54 kW
Numbe
r of
cabinet
s
8 6 8 6
Cabinet
specic
ations
4 PCS: 600 mm x
1100 mm x 2000
mm
4 PCS: 600 mm x
1200 mm x 2000
mm
2 PCS: 600 mm x
1100 mm x 2000
mm
4 PCS: 600 mm x
1200 mm x 2000
mm
4 PCS: 600 mm x
1100 mm x 2000
mm
4 PCS: 600 mm x
1200 mm x 2000
mm
2 PCS: 600 mm x
1100 mm x 2000
mm
4 PCS: 600 mm x
1200 mm x 2000
mm
System
backup
time
15 minutes 20 minutes 15 minutes 20 minutes