Conguration N+X-
Norma
l
Tempe
rature-
CE
N+X-
Low
Tempe
rature-
CE
2N-
Norma
l
Tempe
rature-
CE
2N-
Low
Tempe
rature-
CE
N+X-
Norma
l
Tempe
rature-
CCC
N+X
Low
Tempe
rature-
CCC
2N-
Norma
l
Tempe
rature-
CCC
2N-
Low
Temper
ature-
CCC
Power
density
Total power ≤ 54
kW
6 kW/R: 6 PCS
9 kW/R: 2 PCS
Total power ≤ 54
kW
9 kW/R: 6 PCS
Total power ≤ 54
kW
6 kW/R: 6 PCS
9 kW/R: 2 PCS
Total power ≤ 54
kW
9 kW/R: 6 PCS
Environ
ment
corrosi
on
require
ments
Class A, B, or C environment. Class C environments are more than 500 m
away from strong-corrosion environments (seas, garbage dump areas, and
heavy pollution sources, such as a chemical factory).
Quakep
roof
level
Complies with GR-63-CORE Zone 3.
Salt
spray
corrosi
on
resistan
ce
The pre-fab. module surface is sprayed with special coating and passes the
1440-hour salt spray test by UL.
Storage
temper
ature
range
–40°C to +70°C (excluding batteries. Lithium battery storage temperature
range: 0–40°C)
Storage
humidit
y range
5%–95% RH
Structu
ral
system
Weight Preinstallation weight before delivery: ≤ 14 T; full conguration with
equipment: ≤ 20 T
Aisle
width
Long aisle: 640 mm; cold aisle: 1150 mm; hot aisle (after expansion): ≥ 610
mm
Cabinet
sliding
A 1200 mm deep cabinet can slide 200 mm in both directions.
Power
supply
and
distribu
tion
system
Power
system
380/400/415 V, 50/60 Hz (three-phase, four-wire, and PE)
Input
voltage
range
380/400 V (tolerance: ±15%), 415 V (tolerance: –15% to +10%)
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario)
2 Typical Application Scenarios and Typical
Conguration
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 9