Conguration N+X-
Norma
l
Tempe
rature-
CE
N+X-
Low
Tempe
rature-
CE
2N-
Norma
l
Tempe
rature-
CE
2N-
Low
Tempe
rature-
CE
N+X-
Norma
l
Tempe
rature-
CCC
N+X
Low
Tempe
rature-
CCC
2N-
Norma
l
Tempe
rature-
CCC
2N-
Low
Temper
ature-
CCC
Numbe
r of
inputs
Two inputs
Input
current
250 A
Model
and
number
of UPSs
UPS5000-E, 1
PCS
UPS5000-E, 2 PCS
(1+1 system)
UPS5000-E, 1 PCS UPS5000-E, 2 PCS
(1+1 system)
Power
capacit
y
≤ 60 kVA
(module 2+1
redundancy)
≤ 60 kVA
(module 2+0
redundancy)
≤ 60 kVA
(module 2+1
redundancy)
≤ 60 kVA
(module 2+0
redundancy)
Total
input
surge
protecti
on
Class B, 8/20 µs, I
n
= 30 kA, I
max
= 60 kA
Battery
specic
ations
SmartLi lithium
battery cabinet
(half-capacity
cabinet 40 Ah,
eight battery
modules in one
string) x 1
SmartLi lithium
battery cabinet
(half-capacity
cabinet 40 Ah,
eight battery
modules in one
string) x 2
SmartLi lithium
battery cabinet
(half-capacity
cabinet 40 Ah,
eight battery
modules in one
string) x 1
SmartLi lithium
battery cabinet
(half-capacity
cabinet 40 Ah,
eight battery
modules in one
string) x 2
rPDU
type
IEC standard CCC standard
Cooling
system
Cooling
capacit
y
25 kW @ 37°C, 20% RH/35°C
Redund
ant
congu
ration
3+1 redundancy
Device
dimensi
ons (H
x W x
D)
2000 mm x 300 mm x 1100 mm
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario)
2 Typical Application Scenarios and Typical
Conguration
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 10