7 Fire Extinguishing System
7.1 Overview
Figure 7-1 Fire linkage principle
NO TE
If the pre-fab. module catches re, the extinguishant control panel sends dry contact signals
in the rst stage alarm to the access actuator to release the access control.
If the pre-fab. module catches re, the extinguishant control panel sends 24 V DC signals in
the second stage alarm to the power distribution box used for switching o non-re
extinguishing loads. Then the shunt release trips and the fresh air fan shuts down.
If the pre-fab. module catches re, smoke and heat will trigger the smoke and
heat detectors, which will send re alarm signals to the extinguishant control
panel. Upon receiving the
re alarm signals, the extinguishant control panel
counts down and then opens the electrical actuator on the re extinguisher so
that the
re cylinder discharges extinguishing agent to the protection zone. At the
same time, the extinguishant control panel automatically reports alarms.
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 7 Fire Extinguishing System
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 91

Table of Contents

Other manuals for Huawei FusionDC1000A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionDC1000A and is the answer not in the manual?

Huawei FusionDC1000A Specifications

General IconGeneral
BrandHuawei
ModelFusionDC1000A
CategoryStorage
LanguageEnglish

Related product manuals