Figure 3-9 Cabinet
A cabinet has the following features:
The ventilation rate of the front and rear doors is at least 70%.
An rPDU can be vertically installed at the rear of the cabinet.
The position of each U is marked on the vertical mounting bars.
The front and rear doors are locked and can be unlocked only with dedicated
keys.
The maximum static load of the cabinet is 1800 kg.
Table 3-2 Cabinet technical
specications
Item
Technical Specications
Dimensions (H x W x D) 2000 mm x 600 mm x 1200 mm
2000 mm x 600 mm x 1100 mm
Color Black (PANTONE426C/RAL9005)
Material High-intensity class A carbon cold rolled steel
plate and zinc-coated steel plate
Air channel Front and rear air channels
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 3 Structural system
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 20