Table 4-6 Output electrical specications
Item Specications
Output system Three-phase, four-wire, and PE
Voltage 380 V AC/400 V AC/415 V AC (line voltage)
Regulated voltage
precision
±1% (balanced load)
Output power factor 1
Transfer time Uninterruptible transfer: 0 ms
Interruptible transfer: ≤ 20 ms
Output voltage
imbalance
Voltage imbalance: ±3%; phase imbalance: 120±2°
Overload capability Inverter overload capability:
100% < load ≤ 110%: transfers to bypass mode
after 60 minutes
110% < load ≤ 125%: transfers to bypass mode
after 10 minutes (tolerance ± 0.1 minutes)
125% < load ≤ 150%: transfers to bypass mode
after 1 minute
Load > 150% or a short circuit occurs: run for 200
ms
Bypass overload capability:
30°C environment: works for a long term at 135%
load.
40°C environment: works for a long term at 125%
load.
If the bypass single-phase or three-phase is 150%–
200% overloaded, the bypass can keep working for
5 minutes.
If the bypass single-phase or three-phase is more
than 200% overloaded, the bypass can keep
working for 1 minute.
If the load exceeds 1000%, the bypass can keep
working for 100 ms.
Derating
coecient of
output circuit breakers
40 A circuit breaker: 0.75
63 A circuit breaker: 0.7
Table 4-7 System electrical
specications
Item
Specications
System eciency 95% (linear load)