Figure 5-12 Dimensions of the NetCol500 outdoor unit
Table 5-7 Technical specications of the NetCol500 outdoor unit
Product Model NetCol500-A040MS1E0
Power supply Powered by the indoor unit
Indoor unit model NetCol5000-A025
Operating temperature range –20°C to +55°C (–40°C to +45°C with a low
temperature component)
Fan speed range 10%–100%
Number of fans 1
Dimensions H1 (H2) x W1 (W2) x D (mm) 1096 (665) mm x 1120 (984) mm x 1094 mm
Liquid pipe outer diameter 5/8 inch (15.9 mm)
Gas pipe outer diameter 3/4 inch (19.1 mm)
Certication RoHS, REACH, CE
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)
Altitude 0–4000 m, derated at above 1000 m. For details
about derating data, contact Huawei technical
support.