EasyManua.ls Logo

Huawei FusionModule500

Huawei FusionModule500
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
3 System Architecture
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
53
Table 3-35 BCB_IN and BCB_OUT cascading port pin definitions
Pin
Definition
BCB_IN
Signal
Description
BCB_OUT
Signal
Description
Status
Description
Initial
Status
Descrip
tion
1
OL
Specifies
whether the
BCB
connects to
the signal
output port.
Specifies
whether the
cascaded
BCBs
connect to the
signal input
port.
Grounded:
BCB
connected.
Disconnec
ted: BCB
not
connected.
Discon
nected
Receives
BCB
comman
ds sent
by the
UPS and
supports
BCB
port
cascadin
g
manage
ment.
2
STA
Signal output
port for the
battery circuit
breaker status
Monitors
whether the
cascaded
BCBs are
connected to
the input.
Grounded:
The
battery
circuit
breaker is
ON.
Disconnec
ted: The
battery
circuit
breaker is
OFF.
Discon
nected
3
DRV
Controls battery circuit
breaker trip and receives 12 V
driving signals
0 V: There
is no
driving
signal for
BCB
tripping.
12 V:
There is a
driving
signal for
BCB
tripping.
0 V
4
GND
Secondary side ground
DIP Switch
Table 3-36 DIP switch description
No.
Definition
Description
1
ADDR_1
RS485 communications
address setting
2
ADDR_2
3
ADDR_3
4
ADDR_4

Other manuals for Huawei FusionModule500