Figure 4-9 Querying version information
Pay attention to the following information:
CPLD Version: CPLD version of the compute node
Active iBMC Version: version of the iBMC in the active work space of the
compute node
Backup iBMC Version: version of the iBMC in the standby work space of the
compute node
3. Check whether the versions meet site requirements.
If yes, go to Step 4.
If no, go to Step 3.4.
4. Upgrade the iBMC, BIOS, or CPLD.
For details, see E9000 Server V100R001 Upgrade Guide.
Step 4 Query health status.
Step 5 Query alarm information.
1. Click the compute node in the specific slot and choose Alarm List.
Figure 4-10 Querying alarm information
2. Check whether any alarm is generated.
If yes, handle the alarms.
FusionServer Pro CH121 V5 Compute Node
User Guide
4 Installation and Configuration
Issue 06 (2019-08-10) Copyright © Huawei Technologies Co., Ltd. 81