Alarm
ID
Alarm
Name
Alarm
Severit
y
Possible Cause Suggestion
3830 Temper
ature
and
Humidit
y
Control
Malfunc
tion
Major Cause ID = 1
There are too many
faulty air conditioners
in the battery cabin.
1. Troubleshoot the fault based on the
corresponding troubleshooting
suggestions.
2. On the maintenance screen, check
that the air conditioner is correctly
connected.
3831 The
pressure
of the
re
suppress
ion
module
is
insuci
ent.
Minor Cause ID = 1
The pressure of the re
suppression module is
insucient.
Check the re suppression module and
the pressure gauge, and replace the re
suppression module as soon as possible.
Otherwise, the system will shut down
automatically in three days.