Follow-up Procedure
Step 1 Turn on the power switch of the air conditioner in the cabinet.
Step 2 Check whether the functions are restored.
Check Item Criteria
Alarm information There is no alarm related to the internal fan.
Function Low-speed operation in air supply mode and high-
speed operation in cooling mode
Running data Internal fan status: normal operation
----End
8.2 Replacing an Air Conditioner External Fan
Prerequisites
Fault locating:
a. Log in to the SmartLogger WebUI, CMU WebUI, FusionSolar app, or
management system to view alarm information.
b. Refer to the alarm handling suggestions in the alarm list.
Tools: Phillips insulated torque screwdriver, insulated torque socket wrench,
T20 security torx screwdriver, multimeter, utility knife
Power-o: Turn o the power switch of the air conditioner in the cabinet.
NO TE
The power loop of the ESS does not need to be powered o. You are advised to set
the ESS in standby or shutdown mode during replacement.
Procedure
Step 1 Remove the rear cover of the air conditioner, and use a dedicated T20 security torx
screwdriver to remove the two security torx screws from the bottom.
LUNA2000-200KWH-2H1 Smart String ESS
Maintenance Manual 8 Replacing an Air Conditioner
Issue 02 (2023-02-28) Copyright © Huawei Digital Power Technologies Co., Ltd. 95