Alarm
ID
Alarm
Name
Alarm
Severit
y
Possible Cause Suggestion
3853 ESC
Physical
Location
Failure
Minor Cause ID = 1
ESC physical location
failed.
1. Check whether the network cables
between ESCs are connected properly.
2. Check whether the network cables
between the rst and last ESCs and
the CMU are connected properly.
3. Check whether the RS485 cable
between ESC-1 and the CMU is
connected properly.
3856 Battery
Fault
Protecti
on
Major Cause ID = 1
Some battery packs
are severely faulty,
causing the system to
shut down.
Cause ID = 2
The temperature of
some battery packs is
too low. As a result,
charge capacity is not
reached due to low
temperature
protection.
Maintain the battery pack based on the
alarm and troubleshooting suggestions.
3857 Memory
Abnorm
al
Minor Cause ID = 1
1. The storage space is
insucient.
2. The memory is
faulty.
Contact your technical support.
If ALM-3833 Rectier Fault, ALM-3834 Rectier Protection, ALM-3835 Rectier
Communication Failure, ALM-3836 Rectier Power Failure, or ALM-3837 Rectier Output
Overvoltage is generated, rectify the fault by referring to the following table.
Table 3-2 PSU indicator status and troubleshooting
Indicator
Color Status Description Suggestion
Power
indicator
Green Steady on The PSU has
an AC input.
Normal.
LUNA2000-200KWH-2H1 Smart String ESS
Maintenance Manual 3 Alarm Reference
Issue 02 (2023-02-28) Copyright © Huawei Digital Power Technologies Co., Ltd. 41