Loading...
Figure 8-11 Connecting the AC power cable
----End
8.7 Installing a Single-Phase AC Input Power Cable
(Without External Grid Power Supply)
NO TICE
Obtain the AC auxiliary power from the mains or a reliable power supply. Do not
directly obtain power from the AC side of renewable energy inverters such as PV
inverters and wind power converters.
NO TE
If a UPS or other reliable backup power supply is used, perform the following steps to
connect a single-phase AC input power cable.
Recommended UPS input switch specications: 230/400 V AC 32 A/2P.
Step 1 Remove the short-circuiting bar from 1–2 and insert it to 2–3 on the XU terminal
block.
Step 2 Remove the short-circuiting bar from 4–5 and insert it to 5–6 on the XU terminal
block.
Step 3 Connect the cable.
LUNA2000-200KWH-2H1 Smart String ESS
User Manual 8 Installing Cables
Issue 03 (2023-03-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 110