C Emergency Handling
If an accident (including but not limited to the following) occurs on the site,
ensure the safety of onsite personnel
rst and contact the Company's service
engineers.
Battery Falling or Strong Impact
● If a battery has obvious damage or abnormal odor, smoke, or re occurs,
evacuate the personnel immediately, call emergency services, and contact the
professionals. The professionals can use
re extinguishing facilities to
extinguish the
re under safety protection.
● If the appearance is not deformed or damaged, and there is no obvious
abnormal odor, smoke, or
re, ensure safety and perform the following
operations:
– Warehouse: Evacuate personnel, transfer the battery to an open and safe
place by professionals using mechanical tools, and contact the Company's
service engineers. Leave the battery for an hour and ensure that the
battery temperature is within the room temperature range (tolerance:
±10°C) before handling.
– ESS onsite: Evacuate personnel, close the doors of the ESS, transfer the
battery to an open and safe place by professionals using mechanical
tools, and contact the Company's service engineers. Leave the battery for
an hour before handling.
Flood
● Power
o the system if it is safe to do so.
● If any part of the batteries is submerged in water, do not touch the batteries
to avoid electric shock.
● Do not use batteries that have been soaked in water. Contact a battery
recycling company for disposal.
LUNA2000-200KWH-2H1 Smart String ESS
User Manual C Emergency Handling
Issue 03 (2023-03-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 210