Alarm
ID
Alarm
Name
Alarm
Severit
y
Possible Cause Suggestion
3859 Forced
Dehumi
dicatio
n
Started
Major Cause ID = 1
1. Forced
dehumidication
has been manually
started.
2. To prevent
condensation in the
cabinet after the
cabinet door is
opened, the system
automatically starts
forced
dehumidication.
1. Wait for 20 to 30 minutes for the
system to automatically stop forced
dehumidication.
2. If you manually start forced
dehumidication, the system will shut
down after forced
dehumidication is
completed. You need to manually start
the system.
3. If forced
dehumidication is
automatically started, the system
automatically restores to the original
state after forced
dehumidication is
completed.
3860 IO
Expansi
on
Board
Fault
Minor Cause ID = 1
The IO expansion
board is faulty.
1. Check whether the cable between the
I/O expansion board and the CMU
(RS485-1) is correctly connected. If
not, reconnect the cable.
2. Check whether the power cable of the
I/O expansion board is loose. If yes,
connect the cable securely.
3. If the fault persists, contact your
technical support.
1105 Device
Address
Conict
Major Cause ID = 1
The communication
address of the current
device conicts with
that of the device to
be connected.
Change the local address or the address
of the device to be connected.
If ALM-3833 Rectier Fault, ALM-3834 Rectier Protection, ALM-3835 Rectier
Communication Failure, ALM-3836 Rectier Power Failure, or ALM-3837 Rectier Output
Overvoltage is generated, rectify the fault by referring to the following table.
Table 13-2 PSU indicator status and troubleshooting
Indicator
Color Status Description Suggestion
Power
indicator
Green Steady on The PSU has
an AC input.
Normal.
LUNA2000-200KWH-2H1 Smart String ESS
User Manual 13 Alarm Reference