Table 4-2 Checklist
No. Check Item Acceptance Criteria
1 Cabling space
at the bottom
● If no maintenance space at the bottom is required, it
is recommended that the cabling space at the
bottom of the base support be greater than or equal
to 1.1 m.
● If maintenance space at the bottom is required, it is
recommended that the cabling space at the bottom
of the base support be greater than or equal to 1.3
m.
2 Cable ● The bending radius of a cable is greater than or
equal to 15 times the cable diameter.
● The voltage drop of the farthest loop does not
exceed 5%.
● The sensitivity, voltage level, and thermal stability of
the cables meet the local design specications.
Figure 4-2 Foundation diagram
(1) Highest water level of
the local area in history
(2) Ground (3) Foundation
LUNA2000-213KTL-H0 Smart Power Control System
User Manual 4 Installation
Issue 04 (2024-12-30) Copyright © Huawei Technologies Co., Ltd. 30