Huawei LUNA2000-213KTL-H0 - Installing a PE Cable

Huawei LUNA2000-213KTL-H0
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cable Type Conductor
Cross-Sectional
Area
Outer
Diameter
Descripti
on
AC power
cable
(single-
core)
Single-core outdoor cable and M12
OT/DT terminal
70–240 mm
2
15–35 mm
Communi
cations
cable
FE/COM communications cable: CAT
5E outdoor shielded network cable
and shielded RJ45 connector;
internal resistance ≤ 1.5 ohms/10 m;
material: oxygen-free copper or pure
copper; bending radius ≥ 5 x Cable
diameter
- 4.5–7.5 mm The cable
delivered
with the
device is
1.2 m
long. You
can also
prepare a
cable
according
to site
requirem
ents.
Note [1]: The S
p
value is valid only if the conductors of the PE cable and AC power cable use the
same material. If the materials are dierent, ensure that the conductor cross-sectional area of the
PE cable produces a conductance equivalent to that specied in this table. The specications of
the PE cable are subject to this table or calculated according to IEC 60364-5-54.
Note [2]: Do not use a four-core cable on the AC side. Use a three-core cable or three single-core
cables.
5.3 Installing a PE Cable
Precautions
The grounding shall comply with the local electrical safety regulations.
The PE point of the Smart PCS is located on its enclosure. The PE cable or
grounding bracket must be connected to the PE point.
The PE cable of the Smart PCS must be connected to a nearby ground point.
Do not use a four-core cable to ground the AC side. The ground points of all
Smart PCSs in the same array need to be connected to ensure equipotential
bonding for PE cables.
The resistance of a bond shall be less than or equal to 0.1 ohms.
Procedure
Base support-mounted:
LUNA2000-213KTL-H0 Smart Power Control System
User Manual 5 Cable Installation
Issue 04 (2024-12-30) Copyright © Huawei Technologies Co., Ltd. 48