Table 8-1 Maintenance checklist
Check Item Check Method Maintenance Interval
Alarm Check alarms on the app, SmartLogger, or
management system.
Routine maintenance
● Cleanness of the
air intake vent
● Cleanness of the
air exhaust vent
● Check whether there is dust on the air
intake vents. If necessary, remove and
clean the bae plates.
● Periodically check whether there is dust
buildup at the air exhaust vents. If yes,
clean up dust and foreign matter.
Once every 6 to 12 months
Fan Check whether the fans generate abnormal
noise during operation.
Once every 6 to 12 months
System status ● Check whether the device generates
abnormal sounds during operation.
● Check whether the parameters are
correctly set during operation.
Once every 6 months
Cable connection ● Check whether cables are disconnected
or loose.
● Check whether cables are damaged,
especially whether the cable sheath that
contacts a metal surface is damaged.
● Check whether the unused COM, USB,
and FE ports are locked by waterproof
caps.
6 months after the rst
commissioning and once
every 6 to 12 months after
that
Grounding reliability Check whether the ground cables are
securely grounded.
6 months after the rst
commissioning and once
every 6 to 12 months after
that
Appearance ● Check whether devices or mounting
brackets are damaged or deformed.
● Check whether devices or mounting
brackets are rusty. If there is rust, coat
aking, scratch, paint aking, or other
damage, repair the paint damage by
referring to E How Do I Repair Paint
Damage?. If devices are corroded,
especially when they are installed in a
salt-aected area near the sea, repair
the paint damage promptly to avoid
more severe corrosion.
Once a quarter
Device inspection Check the health status of the Smart PCS
on the SmartLogger. You can rectify faults
based on the inspection logs. For details,
see SmartLogger3000 User Manual.
Once a year
LUNA2000-213KTL-H0 Smart Power Control System
User Manual 8 Device Maintenance
Issue 04 (2024-12-30) Copyright © Huawei Technologies Co., Ltd. 79