Cable specications must meet the requirements in local standards.
Table 5-2 Cable description
No. Cable Type Recommended
Specications
Source
1 DC input
power
cable
Common outdoor PV
cable in the industry
(Recommended model:
PV1-F)
● Conductor cross-
sectional area: 4–6
mm
2
● Cable outer
diameter: 5.5–9
mm
Prepare
d by
the
custom
er
2 AC
output
power
cable
Outdoor copper-core/
aluminum-core cable
● Conductor cross-
sectional area: 16–
50 mm
2
outdoor
copper-core
cable/35–50 mm
2
outdoor aluminum-
core cable
a
● Cable outer
diameter: 16–38
mm
Prepare
d by
the
custom
er
3 (Option
al)
Signal
cable
Outdoor shielded twisted
pair (recommended
model:
DJYP2VP2-2×2×0.75)
● Conductor cross-
sectional area: 0.2–
1 mm
2
● Cable outer
diameter: 4–11 mm
Prepare
d by
the
custom
er
4 PE cable Outdoor single-core
copper cable
Conductor cross-
sectional area: ≥ 16
mm
2
Prepare
d by
the
custom
er
Note a: Five-core cables with a cross-sectional area of 35 mm
2
or 50 mm
2
are
not supported.
If the inverter is used with an optimizer, route AC and DC power cables separately
to prevent AC power cables from interfering with optimizer communication.
SUN2000-(20KTL, 29.9KTL, 30KTL, 36KTL, 40KTL)-
M3
User Manual 5 Electrical Connections
Issue 18 (2024-03-10) Copyright © Huawei Technologies Co., Ltd. 40