C Resetting Password
Step 1 Check that the AC and DC sides of the inverter are both powered on, and
indicators
and are steady green or blinking slowly for more than 3 minutes.
Step 2 Complete the following operations within 4 minutes:
Turn o the AC switch and set DC SWITCH to OFF at the bottom of the inverter. If
the inverter is connected to a battery, turn o the battery switch. Wait until all
LED indicators on the inverter panel turn o.
Turn on the AC switch and set DC SWITCH to ON. Wait about 90s and check that
indicator
is blinking green slowly.
Turn o the AC switch and set DC SWITCH to OFF. Wait until all LED indicators
on the inverter panel turn o.
Turn on the AC switch and set DC SWITCH to ON. Wait until all LED indicators on
the inverter panel blink and then turn o after 30s.
Step 3 Reset the password within 10 minutes. (If no operation is performed within 10
minutes, all parameters of the inverter remain unchanged.)
1. Wait until indicator
blinks green slowly.
2. Connect to the app using the initial WLAN hotspot name (SSID) and initial
password (PSW), which can be obtained from the label on the side of the
inverter.
3. On the login screen, set a new password and log in to the app.
SUN2000-(3KTL-10KTL)-M1 Series
User Manual C Resetting Password
Issue 17 (2024-01-12) Copyright © Huawei Technologies Co., Ltd. 124

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-3KTL-M1 Series and is the answer not in the manual?

Huawei SUN2000-3KTL-M1 Series Specifications

General IconGeneral
Max. efficiency98.4%
European efficiency97.8%
Rated AC output power3000 W
Dimensions (W x H x D)365 x 365 x 156 mm
Operating temperature range-25°C to +60°C
TopologyTransformerless
Protection DegreeIP65
Number of MPP Trackers2
Output Frequency50 Hz / 60 Hz
Cooling MethodNatural Convection
Max. DC Power4500 W
Max. Input Current11 A
Power Factor0.8 leading - 0.8 lagging
Max. apparent power3300 VA
AC output voltage220 V / 230 V / 240 V