Table 5-1 AC Power Cable Specications
Cable Specications Copper-Core Cable Copper-Clad
Aluminum Cable or
Aluminum Alloy
Cable
Conductor cross-
sectional area
(mm
2
)
Range 25–120 25–120
Recomm
ended
value
35 70
Table 5-2 Ground cable specications
Cross-Sectional Area S (mm
2
) of the
AC Power Cable Conductor
Cross-Sectional Area S
P
(mm
2
) of
the PE Cable Conductor
16 < S ≤ 35 S
P
≥ 16
35 < S S
P
≥ S/2
The values in this table are valid only if the PE cable and AC power cable use
the same conductor material. If this is not so, the cross-sectional area of the PE
cable conductor is to be determined in a manner which produces a conductance
equivalent to that which results from the application of this table.
Installing the PE Cable
Step 1 Crimp an OT terminal.
Step 2 Secure the PE cable using the ground screw.
Figure 5-7 Connecting a PE cable
Step 3 (Optional) To enhance the corrosion resistance of a ground terminal, apply silica
gel or paint around the terminal.
----End
SUN2000-(50KTL, 60KTL, 65KTL)-M0
User Manual 5 Electrical Connections
Issue 11 (2024-02-02) Copyright © Huawei Technologies Co., Ltd. 48