Installing the AC Output Power Cable
Step 1 Remove the locking cap from the AC OUTPUT cable gland and then remove the
plug.
Step 2 Route the cable through the cable gland.
1. Select appropriate rubber ttings based on the outer diameter of the AC power
cable to ensure proper sealing.
2. To avoid damaging the rubber tting, do not route a cable with a crimped OT
terminal directly through the rubber tting.
3. Adjusting a cable when the thread-lock sealing nut is tightened will shift the
rubber tting, which will aect the Ingress Protection Rating of the device.
Figure 5-8 Routing a cable
Step 3 Remove an appropriate length of the jacket and insulation layer from the AC
output power cable using a wire stripper.
Ensure that the jacket is in the maintenance compartment.
Figure 5-9 Three-core cable (excluding the ground cable and neutral wire)
(A) Core wire
(B) Insulation layer (C) Jacket
SUN2000-(50KTL, 60KTL, 65KTL)-M0
User Manual 5 Electrical Connections
Issue 11 (2024-02-02) Copyright © Huawei Technologies Co., Ltd. 49