SUN2000-(12KTL, 15KTL, 17KTL, 20KTL)-M0
User Manual
Check the impedance of the output
phase wire to PE, locate the position
with lower impedance and restore
that.
Cause ID = 1
The power grid voltage is
below the lower threshold or
the undervoltage duration
exceeds the value specified by
LVRT.
1. If the alarm occurs occasionally,
the power grid may be abnormal
temporarily. The SUN2000
automatically recovers after
detecting that the power grid
becomes normal.
2. If the alarm occurs frequently,
check whether the grid voltage is
within the acceptable range. If no,
contact the local power operator.
If yes, log in to the mobile phone
app, SmartLogger, or NMS to
modify the grid undervoltage
protection threshold with the
consent of the local power
operator.
3. If the fault persists for a long
time, check the connection
between the AC switch and the
output power cable.