F IPS Test (for Italy CEI0-21 Grid Code only) 
 
Copyright © Huawei Technologies Co., Ltd. 
 
F IPS Test (for Italy CEI0-21 Grid Code 
only) 
Prerequisites 
You have logged in to the app as installer. The initial password is 00000a. Use the initial 
password upon first power-on and change it immediately after login. To ensure account 
security, change the password periodically and keep the new password in mind. Not changing 
the initial password may cause password disclosure. A password left unchanged for a long 
period of time may be stolen or cracked. If a password is lost, devices cannot be accessed. In 
these cases, the user is liable for any loss caused to the PV plant. 
Context 
The Italy CEI0-21 grid code requires an IPS test for the SUN2000. During the IPS test 
process, the SUN2000 consecutively tests the protection thresholds and time for 10-min 
overvoltage, level 1 overvoltage, level 1 undervoltage, level 1 overfrequency, and level 1 
underfrequency. The SUN2000 shuts down after the IPS test starts, and it restarts after the IPS 
test is successful. 
Procedure 
Step 1  On the Home screen, choose Device maintenance > IPS test to access the IPS test screen.