CAUTION
!
WARNING
!
CAUTION
!
WARNING
Do not place the recloser in service until all set-
tings have been programmed and verified.
Failure to comply can result in recloser
misoperation, equipment damage, and personal
injury.
Refer to sections 6 and 7 of this manual for control
programming and operation.
Follow all appropriate OSHA and company
work rules in the installation of this equipment.
All clearances, cover-up and personal protec-
tive equipment must be used. Failure to follow
these instructions may result in damage to
equipment, personal injury or death.
Figure 4-9 – Program/Installation Tag
Installation Preparation
1. Program the unit with the desired
parameters as outlined in Section 6 of
this manual. Record the settings on the
supplied tag and attach the tag to the
operating handle for reference during
installation (Fig. 4-4).
2. Prior to installation, verify vacuum
interrupter integrity by applying 50/60 Hz
40kV AC across the open contacts for 60
seconds. (See Section 7.)
4 — Installation
The unit must be mounted horizontally as il-
lustrated in this manual. Failure to mount in
this attitude may result in improper operation
of the interrupter.
Do not store or lay the recloser in mud, snow or
water.
This could contaminate the insulation over the
interrupter leading to electrical flashover at the
system voltage.
A clean, dry storage environment is recommended.
Hubbell Versa-Tech
®
Single Phase Recloser
Complete this tag when unit is programmed and tie to the operating handle of the unit.
This unit has been programmed to the following settings by: _______________ Date: _____________
Operations to Lockout: 1 2 3 4
Minimum Trip (Amps): ___________ Reset Time (sec): ____________
Min. Response Time (mSec): __________ Cold Load Time: ____________
Sequence Coordination Enabled ❑ Min. Response Enabled for Operation 1 2 3 4
Operation #1: TCC1 TCC2 TCC1 Curve: _____________
Modier: _____________
Operation #2: Reclose Time 1 (sec): ____ Curve: TCC1 TCC2
TCC2 Curve: _____________
Modier: _____________
Operation #3: Reclose Time 2 (sec): ____ Curve: TCC1 TCC2
Operation #4: Reclose Time 3 (sec): ____ Curve: TCC1 TCC2
Location for Installation: _______________________________________________________________
Installed by: ______________________________________________ Date: _____________________