2 — Installation Requirements
Table 2-1 Hardware Torque Specications
User Supplied Requirements
The following is required for installation.
Be sure to have these items on hand
before beginning installation.
Safety Equipment (PPE)
• Hard hat
• Steel-toe work boots
• Appropriate eye protection per your
company’s policy
• Other safety equipment as required by
your company’s policies
Hardware
• 5⁄8 inch (16 mm) galvanized thru-bolts
(or equivalent) long enough to pass
through the center of the utility pole,
plus 3 inches (75 mm)
• Curved galvanized washers for the 5⁄8
inch (16 mm) thru-bolts
• Galvanized nuts for 5⁄8 inch (16 mm)
thru-bolts
• Flat galvanized washers for 1⁄2 inch
(12 mm) and 5⁄8 inch (16 mm)) lag
screws
Electrical
• Terminal pad connectors (if not or-
dered with switch)
• Connector sealing paste (CHANCE ZLN
or equivalent)
• Surge arresters and wire (if needed)
Options
• BP3 By-Pass Switch (for appropriate
Cat. No., see Catalog Section 14B)
• Jumper Wire, 100/400 Amp minimum
capacity (VTLT/VTI)
• M3 Disconnect Switch (for appropriate
Cat. No., see Catalog Section 14B)
Hubbell Power Systems, Inc.
Supplied Requirements
All necessary components and hardware
specific to the installation of the VERSA-
TECH® recloser ordered are included.
Carefully check the components and
hardware items against those listed in
Section 3.
Contact your factory representative if any
parts are missing.
User Supplied Hardware
Item ft-lb N•m Notes
5⁄8 inch (16 mm) thru-bolts N/A N/A Company standards apply
5⁄8 inch (16 mm) lag screws N/A N/A Company standards apply
Terminal connectors N/A N/A Company standards apply
Hubbell Supplied Hardware
Item ft-lb N•m Notes
3/8 inch Crossarm Mount bolts N/A N/A Company standards apply
3/8 inch Insulator Mount bolts 15 20
1/2 inch Terminal bolts 60 81
Hardware Torque
Specications
It is the installing personnel’s respon-
sibility to be sure all threaded fasteners
are installed with the correct torque. All
user supplied hardware is to be torqued
according to company standards.
Recloser and connector hardware torque