Connections
1. Wire brush the jumper conductors and
terminal pads.
2. Apply contact aid, such as CHANCE ZLN
to the contact surfaces. Install the recloser
end of the jumpers. Tighten the terminal
bolts per Table 2-1. if used.
3. Make sure the recloser handle is in the
open position and the contacts are open.
4. Connect the jumpers to the power source.
Tighten the terminal bolts per Table 2-1.
5. The recloser is a bidirectional current
sense device and can be connected
either way to the source or the load side
of the feeder.
NOTE: The unit will not close with the
Non-Reclose handle down if in HLT only
mode.
CAUTION: Avoid applying side loads to
vacuum interrupter end of recloser when
making connections to terminal pads.
Place recloser into service
1. Using appropriately rated hot stick, pull
the red non-reclosing lever to the down
position.
2. Using appropriately rated hot stick, install
the battery pack by inserting; align the
pins in the slots, push and turn clockwise
to lock in place.
3. Ensure all connections are tight and
properly connected.
4. Using an appropriately rated hot stick,
close the unit by pushing the yellow lever
to the extreme up position and release.
You should hear the unit close.
Open the recloser before making final connections.
Failure to comply can result in an electrical arc which can cause
death, personal injury or equipment damage.
Before making any connections to the power line, pull the red non-re-
closing lever down and open the recloser by pulling the yellow handle
to the down position.
Do not open the by-pass switch while the recloser is open.
Failure to comply can result in an electrical arc which can cause
death, personal injury or equipment damage.
Do not ground the recloser.
Grounding the recloser can result in recloser misoperation,
equipment damage and personal injury.
4 — Installation
Electric Shock Hazard. All parts of recloser are energized.
Contact with in service recloser will cause death or se-
vere injury.
Before contacting or servicing the equipment, or working on the
electrical system, isolate and ground the recloser from the electri-
cal system. Verify recloser is de-energized by testing with properly
rated hot sticks and/or rubber gloves and volt meter.
!
DANGER
5. Using an appropriately rated hot stick,
open the by-pass switch
6. Push the red non-reclosing lever to the
up position. The unit is now in normal
operating mode.