3.4 Fieldbus Type Address Map
139
13) Reading of Pressing Current Limit
PLC Output (Address n is the input and output top address for MSCON Gateway Unit.)
Bit
Address
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
n+2
Demand
Command
[1047h]
0 0 0 1 0 0 0 0 0 1 0 0 0 1 1 1
n+3
Data 0
[Position No.]
128
64
32
16
8
4
2
1
n+4
Data 1
[0]
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
n+5
Data 2
[0]
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Reading of Pressing Current Limit
n+6
Data 3
[Axis No.]
4
2
1
PLC Input (Address n is the input and output top address for MSCON Gateway Unit.)
Bit
Address
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
n+2
Response
Command
[1047h]
0 0 0 1 0 0 0 0 0 1 0 0 0 1 1 1
n+3
Data 0
[Position No.]
128
64
32
16
8
4
2
1
n+4
Data 1
[Pressing
Current Limit]
128
64
32
16
8
4
2
1
n+5
Data 2
[0]
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Reading of Pressing Current Limit
n+6
Data 3
[Axis No.]
4
2
1
1 word=16 bit
1 word=16 bit
ME0306-2A