EasyManuals Logo

IBM 9306 User Manual

IBM 9306
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #153 background imageLoading...
Page #153 background image
Rack PDU specifications
When connected to a dedicated power source, the Rack PDU conforms to UL950,
CSA 22.0-950, EN-60950, and IEC-950 standards. The following table contains the
product specifications for the Rack PDU:
Height 43 mm (1.7 in.)
Width 192 mm (7.5 in.)
Depth 221 mm (8.7 in.)
Weight 1.5 kg (3.2 lbs)
Operating temperatures 10°C–35°C (50°F–95°F) at 0–914 m (0–3000 ft)
10°C–32 °C (50°F–90°F°) at 914–2133 m (3000–7000 ft)
Operating humidity 8–80% (non-condensing)
Rated voltage 100–240 V ac, 15 A, single-phase
Rated frequency 50–60 Hz
Maximum power rating 3600 VA
Circuit breaker Two-pole, 15 A with time-delay protection for up to 600 A
input current without nuisance tripping.
Power inlet IEC 320-C20 inlet rated at 16 A (VDE) / 20 A (UL/CSA)
Power outlets Seven IEC 320-C13 outlets rated at 10 A (VDE) / 15 A
(UL/CSA)
Installing Optional Devices 143

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM 9306 and is the answer not in the manual?

IBM 9306 Specifications

General IconGeneral
BrandIBM
Model9306
CategoryServer
LanguageEnglish

Related product manuals