Table 27. A00-FF0 through A24-xxx SRNs (continued)
SRN Description FRU/action
A02-06x Memory Data error (Bad data going to
memory).
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
A02-09x System bus parity error.
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
A02-10x System bus time-out error.
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
A02-11x System bus protocol/transfer error.
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see“POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
A02-12x I/O Host Bridge time-out error.
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
A02-13x I/O Host Bridge address/data parity
error.
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
A03-00x Error log analysis indicates an error
detected by the I/O device, but the
failure could not be isolated.
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
A03-01x I/O Bus Address parity error.
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
Chapter 2. Diagnostics 159