Table 27. A00-FF0 through A24-xxx SRNs (continued)
SRN Description FRU/action
A15-12x Sensor detected redundant power
supply failure.
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
A15-13x Sensor detected a redundant FRU that
has failed.
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
A15-14x Power fault due to unspecified cause.
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
A15-17x Internal redundant power supply
failure.
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
A15-19x Fan failure.
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
A15-20x Non-critical cooling problem, loss of
redundant fan.
1. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
2. If no entry is found, Replace the
system-board.
A15-21x Over temperature condition.
1. Make sure that:
a. The room ambient temperature is within
the system operating environment.
b. There is unrestricted air flow around the
system.
c. All system covers are closed.
d. There are no fan failures
2. Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 84.
3. If no entry is found, Replace the
system-board.
172 Power Systems: Problem Determination and Service Guide for the IBM Power PS700 (8406-70Y)