Table 16. BA000010 to BA400002 Partition firmware SRCs (continued)
v Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved. If an action solves the problem, then you can stop performing the remaining actions.
v See Chapter 3, “Parts listing, Type 8406,” on page 229 to determine which components are CRUs and which
components are FRUs.
Error code Description Action
BA154070 The receive operation failed.
1. Reboot the blade server.
2. If the problem persists:
a. Go to “Checkout procedure” on page
184.
b. Replace the system-board, as described
in “Replacing the FRU system-board
and chassis assembly” on page 260.
BA170000 NVRAMRC initialization failed; device
test failed
1. Go to “Checkout procedure” on page 184.
2. Replace the system-board, as described in
“Replacing the FRU system-board and
chassis assembly” on page 260.
BA170100 NVRAM data validation check failed
1. Shut down the blade server; then, restart it.
2. If the problem persists:
a. Go to “Checkout procedure” on page
184.
b. Replace the system-board, as described
in “Replacing the FRU system-board
and chassis assembly” on page 260.
BA170201 The firmware was unable to expand
target partition - saving configuration
variable
1. Reboot the blade server.
2. If the problem persists:
a. Go to “Checkout procedure” on page
184.
b. Replace the system-board, as described
in “Replacing the FRU system-board
and chassis assembly” on page 260.
BA170202 The firmware was unable to expand
target partition - writing event log entry
1. Reboot the blade server.
2. If the problem persists:
a. Go to “Checkout procedure” on page
184.
b. Replace the system-board, as described
in “Replacing the FRU system-board
and chassis assembly” on page 260.
BA170203 The firmware was unable to expand
target partition - writing VPD data
1. Reboot the blade server.
2. If the problem persists:
a. Go to “Checkout procedure” on page
184.
b. Replace the system-board, as described
in “Replacing the FRU system-board
and chassis assembly” on page 260.
BA170210 Setenv/$Setenv parameter error - name
contains a null character
1. Go to “Checkout procedure” on page 184.
2. Replace the system-board, as described in
“Replacing the FRU system-board and
chassis assembly” on page 260.
72 Power Systems: Problem Determination and Service Guide for the IBM Power PS700 (8406-70Y)