UIN DESCRIPTION EAN
210264
Evomax Multiline
Starter Kit 80/125
5022142102645
210265
Evomax Multiline
Extension Kit 80/125
5022142102652
210268
Evomax Multiline
Starter Kit 100/150
5022142102683
210269
Evomax Multiline
Extension 100/150
5022142102690
EVOMAX MODEL OUT-
PUT
CASCADE SYSTEM LIMITS COMBUSTION PRODUCTS DATA
Model
Maximum
System
Capacity
Maximum
Permissible Header
Pressure ‘A
(Static)
Max rate
CO
Min rate
CO
Temperature
Max
Max Min Hmax Pmax ±0.5 ±0.5
kW kW kW Pa % % C
30 7.5
400 40
9.7 9.0
72
40 10
60 15
80 20
100 25
600 80120 30
150 37. 5
30P 7. 5
400 40 11.4 10.6
40P 10
60P 15
80P 20
At the maximum system capacity the static
pressure generated against the flue resistance
at position [A] must not exceed the value Pmax
quoted in the table below.
* Multiline flue supplied to point A.
Customers are to fabricate / supply B
type flue system to termination point
within flue resistance parameters.
Flue height = 570mm from the top of the first boiler in the system.
Increase the height 29mm for each adjacent boiler.
570mm
599mm
628mm
657mm
686mm
715mm

Other manuals for IDEAL Evomax 30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEAL Evomax 30 and is the answer not in the manual?

IDEAL Evomax 30 Specifications

General IconGeneral
BrandIDEAL
ModelEvomax 30
CategoryBoiler
LanguageEnglish

Related product manuals