EVOMAX MODEL OUT-
PUT
CASCADE SYSTEM LIMITS COMBUSTION PRODUCTS DATA
Model
Maximum
System
Capacity
Maximum
Permissible Header
Pressure ‘A’
(Static)
Max rate
CO₂
Min rate
CO₂
Temperature
Max
Max Min Hmax Pmax ±0.5 ±0.5
kW kW kW Pa % % C
30 7.5
400 40
9.7 9.0
72
40 10
60 15
80 20
100 25
600 80120 30
150 37. 5
30P 7. 5
400 40 11.4 10.6
40P 10
60P 15
80P 20
At the maximum system capacity the static
pressure generated against the flue resistance
at position [A] must not exceed the value Pmax
quoted in the table below.
* Multiline flue supplied to point A.
Customers are to fabricate / supply B
type flue system to termination point
within flue resistance parameters.
Flue height = 570mm from the top of the first boiler in the system.
Increase the height 29mm for each adjacent boiler.
570mm
599mm
628mm
657mm
686mm
715mm