(C) IDM ENERGIESYSTEME GMBH
Installation instructions iPump A 2-7, 3-11
11
description
Monta
e Heizun
sseiti
Heat pump type
iPump A 2-7 iPump A 3-11
Model 230 V
400 V
230 V
Space heating water energy effi ciency class
- 35°C 55°C 35°C 55°C
Energy effi ciency class water heating -
Unit
Performance data acc. to EN 14511 at nominal speed
Heat output at A2°C/W35°C kW 3.90 5.92
Power consumption at A2°C/W35°C kW 0.88 1.35
COP at A2°C/W35°C - 4.42 4.37
Cooling capacity at A35°C/W18°C kW 4.95 7.80
Power consumption at A35°C/W18°C kW 1.03 1.81
EER at A35°C/W18°C - 4.80 4.32
Sound emission
1
Sound power level nominal according to EN 12102 indoor unit
dB(A) 42 45
Sound power level maximum according to EN 12102 indoor unit dB(A) 52 48
Sound power level nominal according to EN 12102 outdoor unit dB(A) 46 50
Sound power level maximum according to EN 12102 outdoor unit dB(A) 49 53
Sound reduced operation outdoor unit (reduced power) dB(A) 46 49
The sound pressure level can be calculated with
the iDM-sound calculation tool
Dimensions indoor unit
Height / Width / Depth
mm 1950 / 600 / 786
Tilted height mm 2150 2150
Weight kg 251 270
Minimum size of installation room
2
(with standard fi lling) m³ 7.27 9.32
Dimensions outdoor unit
Height / Width / Depth
mm 1180 / 1110 / 745
Weight kg 110 113
Hot water tank
Volume of hot water storage tank
l 192
Maximum storage temperature °C 55
Maximum storage temperature with electrical heating unit °C 75
Max. single draw of hot water at 46°C tapping temp. - Heat pump
3
l 260
Max. single draw of hot water at 46°C tapping temp. - Electrical heater
4
l 356
Max. single draw of hot water at 40°C tapping temp. - Heat pump
3
l 315
Max. single draw of hot water at 40°C tapping temp. - Electrical heater
4
l 432
Max. operating pressure heating side bar 3
Max. operating pressure domestic hot water bar 10
Hot water connection R 3/4“
Cold water connection R 3/4“
3.7. Technical data
A
+++
A
++
A
A
+++
A
+++
A